Power consumed by 2 power circuits = 1.5 kW × 2 = 3 kW = 3000 W
Power consumed by 3 light/fan sub-circuit = 800 × 3 = 2400 W
Total Power consumed by circuit (P) = 3000 W + 2400 W = 5400 W
cos Ï• = 0.8
We know that the supply voltage (V) for distribution = 240 W
Now current flow through the circuit (I) is given by,
I= = =28.125A At safety factor
(Sf)=1.5, permissible current
(Ip) flow through the circuit will be,
Ip=I×Sf=28.125×1.5 =42.1875A Since current carrying capacity of the cable should be more than the maximum permissible current.
Hence, the current-carrying capacity of cable will be 45 A