Step 1: Understand the COP formulaThe coefficient of performance (COP) for a refrigerator shows how well it works. The formula is:COP=QH​−QC​QH​​Step 2: Identify what the symbols meanQH​ stands for the heat given to the room (hot side). This is the heat released.QC​ is the heat taken from inside the fridge (cold side). This is the heat extracted, which is 250 J per cycle here.Step 3: Set up the equation with the given numbersWe are told the COP is 5 and QC​ is 250 J . So, we use:5=QH​−250QH​​Step 4: Solve for QH​Multiply both sides by (QH​−250) :5(QH​−250)=QH​Expand:5QH​−1250=QH​Bring QH​ to one side:5QH​−QH​=12504QH​=1250Divide both sides by 4 :QH​=41250​QH​=312.5J